Rack PDU specifications
When connected to a dedicated power source, the Rack PDU conforms to UL950,
CSA 22.0-950, EN-60950, and IEC-950 standards. The following table contains the
product specifications for the Rack PDU:
Height 43 mm (1.7 in.)
Width 192 mm (7.5 in.)
Depth 221 mm (8.7 in.)
Weight 1.5 kg (3.2 lbs)
Operating temperatures 10°C–35°C (50°F–95°F) at 0–914 m (0–3000 ft)
10°C–32 °C (50°F–90°F°) at 914–2133 m (3000–7000 ft)
Operating humidity 8–80% (non-condensing)
Rated voltage 100–240 V ac, 15 A, single-phase
Rated frequency 50–60 Hz
Maximum power rating 3600 VA
Circuit breaker Two-pole, 15 A with time-delay protection for up to 600 A
input current without nuisance tripping.
Power inlet IEC 320-C20 inlet rated at 16 A (VDE) / 20 A (UL/CSA)
Power outlets Seven IEC 320-C13 outlets rated at 10 A (VDE) / 15 A
(UL/CSA)
Installing Optional Devices 143