IBM System x3630 M4 30
Design to ASHRAE Class A3, ambient of 35 °C - 40 °C, with relaxed support:
Support cloud like workload with no performance degradation acceptable (Turbo-Off).
Under no circumstance can any combination of worst case workload and configuration result in
system shutdown or design exposure at 40 °C.
Electrical
Models with 750 W hot-swap power supplies:
100 - 127 (nominal) V AC; 50 Hz or 60 Hz; 8.9 A
200 - 240 (nominal) V AC; 50 Hz or 60 Hz; 4.5 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.14 kVA
Maximum configuration: 0.90 kVA
Models with 550 W hot-swap power supplies:
100 - 127 (nominal) V AC; 50 Hz or 60 Hz; 6.5 A
200 - 240 (nominal) V AC; 50 Hz or 60 Hz; 3.3 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.12 kVA
Maximum configuration: 0.66 kVA
BTU output
Minimum configuration: 406 Btu/hr (119 watts)
Maximum configuration: 2900 Btu/hr (850 watts)
Noise level
6.6 bels (operating).
6.6 bels (idle).